Have any questions?
CONTACT US
EDR-240 Single Output Industrial DIN Rail Power Supply

EDR-240 Single Output Industrial DIN Rail Power Supply

Advantage

> Clean production environment

> Full automatic testing with various tests

> Standardized production process with trained workers

> Low failure ratio and 24-month warranty

> Strong R&D and engineering support

Request a Quote  
EDR-240 Single Output Industrial DIN Rail Power Supply

Features:
Universal AC input/ full range
Built-in active PFC function
Protections: Short circuit/ Over load/ Over voltage/ Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
LED indicator for power on
100% full load burn-in test
Fixed switching frequency at 100KHz
2  year warranty

 

SPECIFICATIONS

OUTPUT

 

Model

NDR-240-24

NDR-240-48

DC Voltage

24V

48V

Rated Current

10A

5A

Current Range

0-10A

0-5A

Rated Power

240W

240W

Ripple & Noise

150mVp-p

150mVp-p

Voltage Adj. Range

24-28V

48-55V

Voltage Tolerance

±1%

±1%

Setup, Rise Time

1500ms,100ms/230VAC   3000ms,100ms/115VAC at full load

Hold Up Time

28ms/230VAC   22ms/115VAC at full load

 

 

INPUT

 

Voltage Range

90~264VAC   47~63Hz; 127~370VDC

AC Current

2.5A/115V   1.3A/230V

Efficiency

84%

85%

Inrush Current

Cold start 20A/115V   35A/230V

Leakage Current

<1mA/240VAC

 

 

PROTECTION

 

Over Load

105%~130%

Protection type: Constant current limiting, recovers automatically after fault condition is removed

Over Voltage

29-33V

56-65V

Protection type: Shut down o/p voltage, re-power on to recover

Over Temp.

100℃±5℃(TSW1)

Protection type: Shut down o/p voltage, recovers automatically after temperature goes down

 

 

ENVIRONMENT

 

Working Temp., Humidity

-10℃~+70℃; 20%~90%RH

Storage Temp., Humidity

-20℃~+85℃; 10%~95%RH

Vibration

10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes

 

 

SAFETY

 

Withstand Voltage

I/P-O/P: 3KVAC   I/P-FG: 1.5KVAC   O/P-FG: 0.5KVAC

Isolation Resistance

I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC

 

 

STANDARD

 

EMC Standard

EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2(EN50082-2)

 

 

OTHERS

 

Dimension

125.5*125.2*100mm(L*W*H)

Weight

1.3Kg

Packing

12pcs/15.5Kg/1.2CUFT

 

 

NOTE

 

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1μ & 47μ parallel capacitor.

3 .Tolerance: includes set up tolerance, line regulation and load regulation.

4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.

5 . Derating may be needed under low input voltages. Please check the derating curve for more details.

Message Feedback
If you have any enquiry about quotation or cooperation,please free to email us at Winston or use the following enquiry form,Our sales representative will contact you within 24 hous.thank you for your interest in our products.
News Center
What Is a Switching Power Supply?
Most electronic devices need specific, steady power to work properly. But the electricity from outlets or batteries often isn't in the right form for these devices. That's where a switching power supply plays a key role. This guide explains exactly what it is, how it works, and why it matters for your devices.
2025-09-06
Can a Motor Soft Starter Adapt to Different Motor Scenarios and Simplify Maintenance?
Motors have hidden risks—like repeated small mechanical shocks that shorten their life, or electrical mismatches that fail compliance checks. Old solutions only fix obvious problems, but a Motor Soft Starter is made to tackle these less-noticed issues.
2025-08-29
Why Motor Soft Starter Is a Must-Have for Modern Motor Control?
Motors power almost every industrial and municipal task—from water pumps to factory conveyors. But their start-up process hides big problems: sudden electrical surges that mess with power grids, and harsh mechanical jolts that break equipment. Old-fashioned starting methods only make these issues worse, leading to frequent breakdowns and costly fixes. A Motor Soft Starter is the simple solution to these headaches.
2025-08-25
The Key Role of Frequency Converter in Electrical
In the vast and ever - evolving field of electrical engineering, the frequency converter has emerged as a transformative and indispensable device. It has revolutionized the way electrical systems oper
2025-06-24

GET A QUOTE

AFFORDABLE PRICE: AS A MANUFACTURER, WE GIVE YOU FACTORY PRICE
Contact Us For Free Sample
×